Inline Dissolved Oxygen and Temperature Analyzer

from $195.00

Model: 6312DTF/6312DTB

Brand: JENCO

Cost-effective water monitoring instrumentation solutions

Features

  • Graphic LCD with manual backlight displays dissolved oxygen, temperature, relay status, and transmitter current mA output simultaneously.

  • Calibration data is stored in memory and is ready for use on power-up.

  • Two sets of isolated and reversible 4 ~ 20 mA current output for dissolved Oxygen and temperature allow it to be used as a proportional output.

  • 4 programmable on/off relays: 3 for dissolved oxygen and 1 for temperature.

  • RS-485 output for remote access allows multiple units to be connected and daisy-chained together.

  • Password protection.

  • IP65

***FREE GROUND SHIPPING, U.S. CUSTOMERS ONLY*** Does not include HI, and AK.

MODEL:
Quantity:
Add To Cart

 

Dissolved Oxygen, Temperature In-line Analyzer. 1/4 DIN, IP65, panel mount DO/Temp analyzer with two sets of 2 wire 4 ~ 20 mA current output, 2 sets of programmable on/off relays, RS-485 output, and backlight

Accesories/Probes for model 6312 DTF ( Contact us for pricing and additional details)

237150: Oxysense 120 Wastewater W/ Membrane & 5-Meter Cable

237450: Oxyferm FDA 120 Sterilizable For Fermentation, No Cable

355088: Oxyferm Cable 3-Meter Cable For Oxyferm 120

355089: Oxyferm Cable 5 Meter Cable For Oxyferm 120

355136: Oxyferm Cable 10 Meter Cable For Oxyferm 120

237135: DO Membrane Kit

 
  • DO Range: 0.000 to 40.000 ppm / 0 to 40000 ppb

    DO Resolution: 0.001 ppm / 1 ppb

    DO Accuracy: ±0.2% F.S.

    DO% saturation Range: 0.0 to 500.0%

    DO% saturation Resolution: 0.1%

    DO% saturation Accuracy: ±0.2% F.S.

    Temperature Range: -10.0 to 120.0 °C

    Temperature Resolution: 0.1 °C

    Temperature Accuracy: ±0.1 °C

    Salinity Compensation: Manual 0.0 to 49.9 ppt

    Pressure Compensation: Manual 600 to 4000 mBar

    Temperature Compensation: Auto -10.0 to 80.0°C, 22K ohm NTC

    Current Output: Two current outputs for dissolved oxygen and temperature (4 ~ 20 mA)

    Current Output Scale: User programmable ,linear

    Maximum Load: 500 ohm

    Isolation Voltage: 500 VDC

    Control Type: 4 ON/OFF controls

    Relay Output: 5 A at 115 VAC or 2.5 A at 220 VAC, resistive load only

    Digital output: RS-485

    Display: 128 x 64 graphical LCD with backlight

    Security: 4-dight password

    Power: 115 VAC or 230 VAC at 50/60 HZ factory pre-set

    Ambient Temperature Range: rom 0 to 50 °C

    Weight/Case: 950 grams / IP 65 ,1/4 DIN case, 148 mm depth